KPM31 Single phase wireless WIFI 4G DIN rail prepaid energy meter

KPM31 Single phase wireless WIFI 4G DIN rail prepaid energy meter


KPM31 single phase din rail prepaid energy meter is in full compliance with the international standard IEC62053:2003 on the 0.5S class energy meter of the relevant technical requirements. It use microelectronic technology and imported large-scale integrated circuits. It also aplicatioon digital sampling processing technology and SMT technology and other advanced technology ,it can be directly and accurately measure the rated frequency of 50/60HZ AC active power ,it use LCD7+1 bit LCD display, with high reliability ,small size,easy installation and so on

Application Occasion

1.Energy and energy efficiency management system.
2.Internal energy consumption statistical analysis and charging statistics basis.
3.Energy metering,automatic meter reading system.
4.Intelligent distribution management system.




 

140x140
  • Single phase din rail prepaid energy meter
  • Full electrical parameter measurement:
  • U, I, F, PF, P;
  • active and reactive energy, etc.
140x140
  • High accuracy:
  • Voltage accuracy Class 0.2
  • Current accuracy Class 0.2
  • Power accuracy Class 0.5
  • Active energy Class 0.5
  • Reactive energy accuracy Class 2.0
140x140
  • Record function:
  • 12 month energy consumption frozen data;
  • Meter working time, load time statics.
140x140
  • Other features:
  • Communication:WIFI/4G based on MQTT; RS485 based on MODBUS RTU
  • Installation method:DIN rail 35MM
  • Optional remote control

 

KPM31 single phase din rail smart energy meter


Input Voltage

Working Voltage

AC 110V/220V

Frequency range

45-65Hz

Rated power consumption

KPM31A:<2VA,KPM31B:<3VA

Input current

Rated current

5-63A

Frequency range

45-65Hz

Measurement accuracy

Voltage

±0.2%(0.01V)

Current

±0.2%(0.01A)

Active power

±0.5%(0.01W)

Reactive power

±2.0%(0.01var)

Power factor

±0.5%(0.001)

Frequency

±0.02 (0.01Hz)

Active energy

±0.5%(0.1kwh)

Reactive energy

±2.0%(0.1kvarh)

Clock

Clock accuracy

<0.5S/D

Communication

communication port

RS485,Photoelectric isolation interface

Communication protocol

Modbus-RTU, 1200-19200BPS

Working environment

Operating temperature

-10℃ ~ +55℃

Storage temperature

-20℃ ~ +75℃

Relative humidity

5% ~ 95% No condensation

Electrical

insulation

Dielectric strength

Power frequency voltage AC 2kV, working time 1 min

Insulation resistance

>50MΩ

Impact voltage

5kV (Peak),1.2/50us

Electromagnetic Compatibility

Electrostatic discharge immunity

IEC61000-4-2, level 4

Fast pulse group immunity

IEC61000-4-4, level 4

Surge immunity

IEC61000-4-5, level 4

Power frequency magnetic field immunity

IEC61000-4-8, level 4

KPM31A single phase din rail smart energy meter direct access typical wiring diagram

 

KPM31B single phase din rail smart energy meter direct access tipycal wiring diagram