The busbar split core current transformer is designed for the electrical installation without disassembling and disconnecting the existing main bus or cable. The secondary output 5A or 1A standard current signal matches the input port of the power meter's measurement and control terminal. It’s applicable to electric power meter, switch cabinet, control cabinet and other power measurement and control equipment.




 

140x140
  • Busbar Split Core Current Transformer
  • 1. Open-close type installation, easy to install and disassemble.
  • 2. Stable performance, light weight.
  • 3. Open-close type design, no to need to cut off the power. 
140x140
  • 1. Flame retardant plastic shell.
  • 2. Pure copper coil and iron core made
  • 3. Durable and practical
  • 4. Secondary rated output 5A, 1A is avaible if u need. 
140x140
  • Multiple core size for option:
  • 50*80mm, 80*80mm, 80*120mm, 60*100mm, 80*160mm.
140x140
  • Primary current input 300A-5000A.
  • Secondary current output 5A/1A. 

 

Model Current Accuracy  Load (VA) Frequency (Hz)
KP-FCT30*20  100/5A 1 1 50/60Hz
150/5A 1 1
200/5A 0.5 1.5
250/5A 0.5 1.5
300/5A 0.5 1.5
400/5A 0.5 2.5
KP-FCT80*50  250/5 1 1.5  
300/5 1 1.5  
400/5 0.5 1.5  
500/5 0.5 2.5 50/60Hz
600/5 0.5 2.5  
750/5 0.5 2.5  
800/5 0.5 2.5  
1000/5 0.5 5  
KP-FCT80*80  250/5 1 1.5 50/60Hz
300/5 1 1.5
400/5 0.5 1.5
500/5 0.5 2.5
600/5 0.5 2.5
750/5 0.5 2.5
800/5 0.5 2.5
1000/5 0.5 5
KP-FCT120*80  500/5 0.5 2.5 50/60Hz
600/5 0.5 2.5
750/5 0.5 2.5
800/5 0.5 2.5
1000/5 0.5 5
1200/5 0.5 7.5
1250/5 0.5 7.5
1500/5 0.5 7.5
KP-KCT100*60  800/5 0.5 2.5 50/60Hz
1000/5 0.5 10
1500/5 0.5 15
2000/5 0.2 15
2500/5 0.2 15
3000/5 0.2 20
KP-KCT160*80  1000/5 0.5 10 50/60Hz
1500/5 0.5 15
2000/5 0.2 15
2500/5 0.2 15
3000/5 0.2 20
4000/5 0.2 20
5000/5 0.2 20
 
Electrical Parameters Mechanical parameters
Frequency 50-400Hz Shell PC/UL94-V0
Rated input 5A-5000A Framework PBT
Measuring range 10%In-120%In Iron core Silicon steel
Rated output 0-5A Inner frame Winding
Ratio difference ≤ ± 0.5% Installation Open mounting
Angle difference ≤ ±30min Working temperature -25~+75
Dielectric strength 2.5KV/1mA/1min Storage humidity ≤50%
Insulation resistance DC500V/100MΩ min Output wiring Terminal

 

 

 