KPM10 Three phase multifunction digital power meter
Working power source |
Operating Voltage |
AC 85-265V/ DC 80-300V |
Rated power consumption |
< 3VA |
|
Input voltage |
Rated voltage |
57.7/100V,220/380V |
Overvoltage capability |
1.2 times rated voltage allowed, continuous work; 2 times the rated voltage allowed 10s |
|
Rated power consumption |
<0.5VA(per phase) |
|
Measurement range |
LN:50~260VAC |
|
Input current |
Rated current |
Default 5A, input range 1-6A; optional 1A, input range 1-1.2A |
Overload capacity |
1.2 times rated current allowed, continuous work; 20 times the rated current allowed 1s |
|
Rated power consumption |
<0.75VA/phase(5A); <0.45VA/phase(1A) |
|
Measurement range |
5A:0~6A; 1A:0~1.2A |
|
Power quality monitor |
Harmonic measurement |
Voltage/current 2-21st harmonic distortion rate, |
Harmonic distortion rate |
Phase voltage, phase current |
|
Imbalance rate |
Voltage, current |
|
Measurement accuracy |
Voltage |
±0.2%(0.01V) |
Current |
±0.2%(0.01A) |
|
Active power |
±0.5%(0.01W) |
|
Reactive power |
±2.0%(0.01var) |
|
Power factor |
±0.5%(0.01) |
|
Frequency |
±0.02(0.01Hz) |
|
Active energy |
±0.5S(0.1kwh) |
|
Reactive energy |
±2.0%(0.1kvarh) |
|
Communication |
communication port |
RS485,Photoelectric isolation interface |
Communication protocol |
Modbus-RTU, 1200-38400BPS |
|
DI & DO |
Switch value input |
2-way passive main line contact DI input, internal supply DC24V power supply |
Relay output |
2-Way DO output, contact capacity 250VAC / 5A, 30VDC / 5A |
|
Working environment |
Operating temperature |
-25℃ ~ +70℃ |
Storage temperature |
-30℃ ~ +75℃ |
|
Relative humidity |
5% ~ 95% No condensation |
|
Altitude |
Not more than 4000m |
|
Electrical insulation |
Dielectric strength |
Power frequency voltage AC 2kV, working time 1 min |
Insulation resistance |
>50MΩ |
|
Impact voltage |
5kV (Peak),1.2/50us |
|
Electromagnetic Compatibility |
Electrostatic discharge immunity |
IEC61000-4-3, level 4 |
Fast pulse group immunity |
IEC61000-4-4, level 4 |
|
Surge immunity |
IEC61000-4-5, level 4 |
|
Power frequency magnetic field immunity |
IEC61000-4-8, level 4 |
KPM10RK Low-voltage three-phase three-wire typical wiring diagram
KPM10RK Low-voltage three-phase three-wire typical wiring diagram
KPM31D Socket type outdoor single phase electricity ANSI meter is in full compliance with the international standard ANSI_C12.21-2006 on the 0.5S
KPM312 Three Phase Multi Channel Energy Meter adopts DIN 35MM rail type installation structure and LCD display. It integrates 4 channels three-phase e
KPM37 Wireless 4G WiFi LoRa Din Rail Three Phase Energy Meter adopts DIN 35MM rail type installation structure and LCD display. It integrates three-ph
KPM33 Three-phase DIN rail smart energy meter with DIN35mm rail installation structure,LCD display,measurement of electrical energy and other electric
KPM31C Single phase 4G DIN rail prepaid energy meter is in full compliance with the international standard IEC62053:2003 on the 0.5S class energy